It's not a typo because 400A is indeed the highest tier residential service BC Hydro currently offers[0]. 400A is also in the right ballpark for the amount of equipment he describes.

[0] https://app.bchydro.com/accounts-billing/electrical-connecti...



The copper coming from "something" will be at least 1/2 inch thick, probably more so that it doesn't lose voltage. We're probably talking a 7/0 cable where 4/0 would be bare minimum.


Probably larger than that. If they’re 200m from the transformer, 400A service requires (3) 1000kcmil cables per leg. 100m drops it to (3) 350kcmil which is still pretty beefy


Oh, I believe that. The number is, well, unbelievable high, so I dismissed it as wrong without further thinking.